CHAPTER 5: SETTINGS
SYSTEM SETUP
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
5-181
5
PMU 1 TIMED TRIGGER POSITION
— Specifies the amount of pre-trigger data as a percent of the entire record. This setting
applies only to the timed mode of recording.
5.5.7.19 Aggregators
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1(4)
PMU AGGREGATOR1 PROTOCOL
— Selects if the IEEE C37.118 or IEC 61850-90-5 technical report is used. Because one
protocol is supported at a time in a device, this setting applies to all PMU aggregators.
PMU AGGREGATOR1 IDCODE
— Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output stream, this
identifies the ID of the aggregator, which is only used if there is more than 1 PMU mapped into an aggregator.
PMU AGGREGATOR1 PMU1
— If set to “Yes,” aggregator 1 includes the PMU1 data set in the reporting data stream.
AGGREGATOR1 does not include PMU1 data set in the report if set to “No.”
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1(4)
C37.118 AGGR 1(4)
CONFIGURATION
PMU AGGREGATOR 1
PMU AGGREGATOR 1
PROTOCOL: NONE
Range: NONE, 37.118, 90-5
PMU AGGREGATOR 1
IDCODE: 1
Range: 1 to 65534 in steps of 1
PMU AGGREGATOR 1
INCLUDE PMU1: No
Range: No, Yes
PMU AGGREGATOR 1
INCLUDE PMU2: No
Range: No, Yes
PMU AGGREGATOR 1
INCLUDE PMU3: No
Range: No, Yes
PMU AGGREGATOR 1
INCLUDE PMU4: No
Range: No, Yes
PMU AGGREGATOR 1
INCLUDE PMU5: No
Range: No, Yes
PMU AGGREGATOR 1
INCLUDE PMU6: No
Range: No, Yes
C37.118 AGGR 1
CONFIGURATION
See below
90-5 AGGR 1
CONFIGURATION
See below
When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None are
set to the last protocol saved (that is, IEEE C37.118 or IEC 61850-90-5) to any aggregators, as both IEEE C37.118 and
IEC 61850-90-5 simultaneous streaming is not possible.
Only PMUs with same reporting rate can be assigned to the same PMU AGGREGATOR.
C37.118 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
TCP PORT: 4712
Range: 0 to 65534
PMU AGGREGATOR 1:
UDP PORT: 4713
Range: 0 to 65534
PMU AGGREGATOR 1:
PDC CONTROL: Disabled
Range: Disabled, Enabled