5-208
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
Figure 5-110: Non-volatile latch operation table (N = 1 to 16) and logic
5.6.9 FlexMath
SETTINGS
FLEXLOGIC
FLEXMATH
SUMMATOR
SUMMATOR 1(6)
Latch n type Latch n
set
Latch n
reset
Latch n
on
Latch n
off
Reset
Dominant
ON
OFF
ON
OFF
OFF
OFF
Previous
State
Previous
State
ON
ON
OFF
ON
OFF
ON
OFF
ON
Set
Dominant
ON
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
Previous
State
Previous
State
OFF
ON
OFF
ON
SUMMATOR 1
SUMMATOR 1 FUNCTION:
Disabled
Range: Disabled, Enabled
SUMMATOR 1 INPUT
MODE: SIGNED
Range: SIGNED, ABSOLUTE
SUMMATOR 1 HOLD:
Off
Range: FlexLogic operand
SUMMATOR 1 PICKUP:
1000.000
Range: –2000000.000 to 2000000.000 in steps of
0.001
SUMMATOR 1
HYSTERESIS: 3.0%
Range: 0.1 to 50.0% in steps of 0.1
SUMMATOR 1 UNITS:
Range: up to four alphanumeric characters
SUMMATOR 1 PU BASE:
1
Range: 1 to 2000000 in steps of 1
SUMMATOR 1 INPUT 1:
Off
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
SUMMATOR 1 INPUT 2:
Off
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.