5-182
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
PMU AGGREGATOR 1 TCP PORT
— Selects the TCP port number to be used by this aggregator for network reporting. All ports,
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 UDP PORT
— Selects the UDP port number to be used by this aggregator for network reporting. All ports,
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 PDC CONTROL
— The synchrophasor standard allows for user-defined controls originating at the PDC, to
be executed on the PMU. The control is accomplished via an extended command frame. The relay decodes the first word
of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator supports 16 FlexLogic
operands, as shown in the table. The operands are asserted for five seconds following reception of the command frame. If
the new command frame arrives within the five-second period, the FlexLogic operands are updated, and the five-second
timer restarts. This setting enables or disables the control. When enabled, all 16 operands for each aggregator are active;
when disabled, all 16 operands for each aggregator remain reset.
Table 5-21: FlexLogic operands supported by aggregator
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1(4)
90-5 AGGR 1(4)
CONFIGURATION
PMU AGGREGATOR 1 NAME
— A user-defined visible string of characters (maximum 56) to identify the source of the stream.
This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the IEC 61850
MSVID filed in the output stream. The field allows 65 characters, but uses the first 56 characters.
AGGREGATOR 1: PHYSICAL PORT
— This setting determines the physical ports through which the synchrophasor traffic is
transmitted. The range is 1, 2, 3.
PMU AGGREGATOR 1: UDP PORT
— This setting selects the UDP port number that is used by this dataset for network reporting.
A default setting value for IEC 6150-90-5 is provided.
Operand type
Operand syntax
Operand description
ELEMENT:
Synchrophasor, phasor data,
concentrator
AGTR1 PDC CNTRL 1
Phasor data concentrator asserts control bit 1, as
received via the network
as above
AGTR1 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network
as above
AGTR1 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network
as above
AGTR2 PDC CNTRL 1
Phasor data concentrator asserts control bit 1 as
received via the network
as above
AGTR2 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network
as above
AGTR2 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network
90-5 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
NAME:
Range: 56-character ASCII text (blank by default)
PMU AGGREGATOR 1
PORT: 1
Range: 1, 2, 3
PMU AGGREGATOR 1
UDP PORT: 102
Range: 0 to 65534 in steps of 1
PMU AGGREGATOR 1
NUMBER OF ASDUs: 1
Range: 1 to 4