5
5.7 Grouped elements
5.7.1 Overview
Each protection element can be assigned up to six sets of settings with designations 1 to 6. The performance of these
elements is defined by the active setting group at a given time. Multiple setting groups allow the user to conveniently
change protection settings for different operating situations (for example, altered power system configuration or season of
the year). The active setting group can be preset or selected in the
SETTING GROUPS
menu (see the Control Elements section
later in this chapter). See also the Introduction to Elements section at the beginning of this chapter.
5.7.2 Setting group 1
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
5.7.3 Power swing detect (ANSI 68)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
POWER SWING DETECT
SETTING GROUP 1
POWER SWING
DETECT
See below
PHASE CURRENT
NEUTRAL CURRENT
GROUND CURRENT
VOLTAGE ELEMENTS
SUPERVISING
ELEMENTS
POWER
POWER SWING
DETECT
POWER SWING
FUNCTION: Disabled
Range: Disabled, Enabled
POWER SWING
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
POWER SWING
SHAPE: Mho Shape
Range: Mho Shape, Quad Shape
POWER SWING
MODE: Two Step
Range: Two Step, Three Step
POWER SWING
SUPV: 0.600 pu
Range: 0.050 to 30.000 pu in steps of 0.001
POWER SW I2 SUPV ENAB:
Off
Range: FlexLogic operand