CHAPTER 5: SETTINGS
FLEXLOGIC
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
5-209
5
Six identical summators are available in each N60 device.
Each summator has six inputs and a scaling factor is provided for each input. The scaling factors can be set to +1 and –1,
allowing straight addition and subtraction of the inputs. A FlexLogic operand provided for each input can dynamically
include/exclude the input from calculations.
The summator performs the following operation:
Y = P
1
S
1
X
1
+ P
2
S
2
X
2
+ ... + P
6
S
6
X
6
Eq. 5-8
where
X represents the programmed input of summator N (determined by the
SUMMATOR N INPUT1(6)
settings)
S represents the programmed scale of summator N (determined by the
SUMMATOR N SCALE 1(6)
settings)
P represents the programmed position of summator N (determined by the
SUMMATOR N POS1(6)
settings)
The resulting Y value can be set as absolute or signed, allowing switching between the signed and absolute values of the
summator.
A user-programmable threshold is available to compare the Y value with a constant when driving the output operand:
Op
≡
(Y > D) or Op
≡
(abs(Y) > D)
Eq. 5-9
where
Op is an output FlexLogic operand (for example,
SUMMATOR 1 OP
)
D is the user-programmable threshold (for example,
SUMMATOR 1 PICKUP
)
Y is the operating value derived earlier (for example,
SUMMATOR 1 OUTPUT
)
The Y value becomes a FlexAnalog parameter itself. As such, it can be used by other summators, FlexElements, and user-
programmable displays.
The settings for summator 1 are described as follows. The descriptions apply to all six summators.
SUMMATOR 1 FUNCTION
— When set to “Enabled,” this setting allows summator functionality.
SUMMATOR 1 INPUT MODE
— Determines how the output data is formatted. When set to “Signed,” the sign (positive/
negative) of the input data summation remains intact. When set to “Absolute,” the absolute value of the summation is used
as the output value.
SUMMATOR 1 HOLD
— The output value to the summator is frozen when the FlexLogic operand assigned to this setting is
active (on).
SUMMATOR 1 PICKUP
— When the output value of the summator is greater than the value assigned to this setting, the
SUMMATOR 1 OP
FlexLogic operand is activated (set to on).
SUMMATOR 1 INPUT 6:
Off
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
SUMMATOR 1 SCALE 1:
1.000000
Range: –2000.000000 to 2000.000000 in steps of
0.000001
SUMMATOR 1 SCALE 2:
1.000000
Range: –2000.000000 to 2000.000000 in steps of
0.000001
SUMMATOR 1 SCALE 6:
1.000000
Range: –2000.000000 to 2000.000000 in steps of
0.000001
SUMMATOR 1 POS 1:
Off
Range: FlexLogic operand
SUMMATOR 1 POS 2:
Off
Range: FlexLogic operand
SUMMATOR 1 POS 6:
Off
Range: FlexLogic operand
SUMMATOR 1 EVENTS:
Disabled
Range: Disabled, Enabled