CHAPTER 5: SETTINGS
GROUPED ELEMENTS
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
5-229
5
Figure 5-119: Phase time overcurrent 1 logic
5.7.4.4 Phase instantaneous overcurrent (ANSI 50P, IEC PIOC)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE CURRENT
PHASE IOC 1(12)
PHASE IOC 1
PHASE IOC1
FUNCTION: Disabled
Range: Disabled, Enabled
PHASE IOC1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
PHASE IOC1
PICKUP: 1.000 pu
Range: 0.005 to 30.000 pu in steps of 0.001
PHASE IOC1 PICKUP
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
PHASE IOC1 RESET
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
PHASE IOC1 BLOCK A:
Off
Range: FlexLogic operand
PHASE IOC1 BLOCK C:
Off
Range: FlexLogic operand
PHASE IOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
PHASE IOC1
EVENTS: Disabled
Range: Disabled, Enabled