5-80
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Figure 5-32: IEC 61850 buffered report panel
An IEC 61850 Report server is an efficient method to deliver generic substation event information from a single server to a
single client, such as a supervisory control IED. A Configurable Report is a UR element implementing an IEC 61850 Report
server, either of the buffered or unbuffered kind. The following table lists the number of Configurable Report elements.
Each Configurable Report element can report the values of up to 64 FlexLogic or FlexAnalog operands. Buffered report
elements queue value changes that occur while the client is offline and delivered when the client re-connects. Up to 512
events can be queued. Unbuffered control blocks purge all value change events when the connection to the client is lost;
any events that occur while the client is not connected are lost.
Table 5-11: Number of report elements
Configurable Reports interoperate with any client device of any manufacturer that conforms to the IEC 61850 edition 1.0
or 2.0 report client requirements.
The entities whose values are reported by a Configurable Report are known as members. The members are itemized in an
ordered list known as a data set. Each Configurable Report can use any one of the data sets provided that no more than
four data sets are used for reports. This restriction is to limit the amount of processing power that can be allocated to
reporting.
Each enabled Configurable Report transmits an update to its client whenever a value change is detected in one or more of
its members. Also, the control block can be configured to send integrity reports containing the present value of all
members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not
read and acknowledged by the client to be retransmitted.
Number
Buffered reports
30
Unbuffered reports
18