5-22
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Session settings
SETTINGS
PRODUCT SETUP
SECURITY
SESSION SETTINGS
SESSION LOCKOUT
— This setting specifies the number of failed authentications before the device blocks subsequent
authentication attempts for the lockout period. A value of zero means lockout is disabled.
SESSION LOCKOUT PERIOD
— This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
there is no lockout period.
Restore defaults
SETTINGS
PRODUCT SETUP
SECURITY
RESTORE DEFAULTS
LOAD FACTORY DEFAULTS
— This setting is used to reset all the settings, communication, and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
Supervisory
SETTINGS
PRODUCT SETUP
SECURITY
SUPERVISORY
The Supervisory menu settings are available for Supervisor role only, or if the Supervisor role is disabled then for the
Administrator role only.
In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry,
the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated password.
In CyberSentry, password encryption is not supported.
SESSION
SETTINGS
SESSION LOCKOUT:
3
Range: 0 to 99
SESSION LOCKOUT
PERIOD: 3 min
Range: 0 to 9999 minutes
RESTORE DEFAULTS
LOAD FACTORY
DEFAULTS: No
Range: Yes, No
SUPERVISORY
DEVICE
AUTHENTICATION: Yes
Range: Yes, No
BYPASS ACCESS:
Disabled
Range: Local, Remote, Local and Remote, Disabled,
Pushbuttons
LOCK RELAY:
Disabled
Range: Enabled, Disabled
FACTORY SERVICE
MODE: Disabled
Range: Enabled, Disabled
SELF TESTS
See below
SUPERVISOR ROLE:
Disabled
Range: Enabled, Disabled
SERIAL INACTIVITY
TIMEOUT: 1 min
Range: 1 to 9999 minutes