9-6
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CONVERT DEVICE SETTINGS
CHAPTER 9: MAINTENANCE
9
Figure 9-5: Upgrade settings
4.
Review the conversion report. The values of all settings that have been defaulted during conversion are not listed in
the conversion report; to find the value of a setting before conversion, inspect the device backup file made before
conversion.
In the example shown here, settings have been reset to factory defaults and several settings are new in firmware
version 7.6 under
Settings > System Setup > Switches
and
Breakers
.
Figure 9-6: Conversion report
5.
Change settings in the new file, for example by looking at the original file.
6.
Write the converted file to the device, for example by dragging and dropping from the Offline Window to the Online
Window.
7.
Check settings and operation.