5-284
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-155: Frequency rate of change logic
5.8.12 Digitizers
SETTINGS
CONTROL ELEMENTS
DIGITIZERS
DIGITIZER 1(5)
There are five digitizer elements. The digitizer truncates the input signal to user-specified symmetrical limits and digitizes
the outcome with an eight-bit resolution. The following equations describe the basic operation of the element.
Eq. 5-29
Eq. 5-30
where
x is an input signal specified by the
DIGITIZER 1(5) SOURCE
setting
LIMIT is defined by the
DIGITIZER 1(5) LIMIT
setting
round is an operand that rounds up to the nearest integer
N
out
is an integer output of the digitizer (from –127 to 127)
The figure illustrates the output characteristic of the digitizer element.
DIGITIZER 1
DIGITIZER 1
FUNCTION: Disabled
Range: Disabled, Enabled
DIGITIZER 1 SRC:
Off
Range: Off, any FlexAnalog parameter
DIGITIZER 1
LIMIT: 1.000 pu
Range: 0.050 to 90.000 pu in steps of 0.001