CHAPTER 5: SETTINGS
PRODUCT SETUP
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
5-85
5
Figure 5-35: Member right-click
DataSet01 name
Range: 0 to 32 VisibleString characters
Default: DataSet01
The value entered sets the name of the data set, which is required to be unique within the UR for proper operation. The
value entered sets the name of the data set, which is required to be unique within the UR for proper operation. Fast
datasets start with TT6, and slow datasets start with TT3. Up to six fast datasets are allowed. Up to four fast GOOSE
datasets are allowed.
An ObjectReference to the data set consists of a string that is the concatenation of "<LDName>/LLN0$" and the
DataSet01 name setting value. An ObjectReference to the data set is published in the datSet field of TxGOOSE messages,
and it can be used by subscribers to discriminate the messages of that TxGOOSE from other GOOSE messages. An
ObjectReference to the data set is optionally published in the DatSet field of Report messages. Valid characters are
upper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.
DataSet01 shared by
Range: 0 to 32 VisibleString characters
Default:
Names of all control blocks that use this DataSet. Read-only field.
DataSet01 Member1
Range: End of List or any instantiated 61850 data object or data attribute with Functional Constraint ST or MX
Default: End of List
This setting specifies the first member in TxGOOSE1 messages. There is a similar setting for each of the up to 64
members that the UR allows in a Dataset. Only values of members before the first set to End of List are published.
Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert.
Product setup
Navigate to
Settings > Product Setup > Communications > IEC 61850 > Product Setup
.