CHAPTER 5: SETTINGS
PRODUCT SETUP
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
5-13
5
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the
Settings > Product
Setup > Security
menu item to display the security settings window.
The
Remote Settings Authorized
setting is used for remote (Ethernet or RS485 interface) setting access supervision. If this
setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is required.
If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is provided. If this
setting is any other FlexLogic operand, then the operand must be asserted (on) prior to providing the remote setting
password to gain setting access.
The
Access Authorized Timeout
setting represents the timeout delay remote setting access. It applies when the
Remote
Settings Authorized
setting is programmed to any operand except “On” or “Off.” The state of the FlexLogic operand is
continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted, and the timer
programmed with the
Access Authorized Timeout
setting value is started. When this timer expires, remote setting access
is denied immediately. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer updates every five seconds.
5.3.1.3 EnerVista security
Enable the security management system
The EnerVista security system allows an administrator to manage access privileges of multiple users of EnerVista.
It is disabled by default to allow access to the device immediately after installation. When security is disabled, all users
have administrator access. GE recommends enabling the EnerVista security before placing the device in service.