5-36
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Number of Decimals
Range: 0 to 10 in steps of 1
Default: 3
This setting specifies the number of decimal places in the displayed metered value.
5.3.3.4 Single-line diagram editor
The path is
Settings > Product Setup > Graphical Panel > Single Line Diagram Editor
. Use is explained in the Interfaces
chapter.
5.3.3.5 Annunciator editor
The annunciator editor is used to create annunciator content for the graphical front panel, including alarms and actual
values. Use is explained in the Interfaces chapter.
The path is
Settings > Product Setup > Graphical Panel > Annunciator Editor
.
To add an alarm, access the Annunciator Editor, configure the layout and page name, configure the alarm, set the text and
color, then save. On the graphical front panel, view the alarm by pressing the
Annunciator
Tab pushbutton at the bottom
of the
Home
page. (Alarms do not display automatically.) Acknowledge or reset the alarm by navigating to it with the arrow
pushbuttons, then press the
ENTER
or
RESET
pushbutton.
The figure shows alarms for basic functions. The last annunciator page is named Device Alarms. Alarms are set for the
device being offline, Ethernet issues, unauthorized access, battery failure, and high ambient temperature. They can reset
themselves when conditions return to normal, except for unauthorized access and temperature monitoring, which require
the alarms to be acknowledged. The self-test error functions have also been enabled under
Settings > Product Setup >
User-Programmable Self Tests
(not shown). When the alarms are triggered, they display with a red background. An alarm
is acknowledged by using the arrow keys on the graphical front panel then pressing the
Enter
button.