CHAPTER 5: SETTINGS
TRANSDUCER INPUTS/OUTPUTS
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
5-311
5
Figure 5-171: Teleprotection input/output processing
5.10 Transducer inputs/outputs
5.10.1 DCmA inputs
SETTINGS
TRANSDUCER I/O
DCMA INPUTS
DCMA INPUT F1(W8)
Hardware and software are provided to receive signals from external transducers and to convert these signals into a
digital format for use as required. The relay accepts inputs in the range of –1 to +20 mA DC, suitable for use with most
common transducer output ranges; all inputs are assumed to be linear over the complete range. Hardware details are
contained in chapter 3.
DCMA INPUT F1
DCMA INPUT F1
FUNCTION: Disabled
Range: Disabled, Enabled
DCMA INPUT F1 ID:
DCMA Ip 1
Range: up to 20 alphanumeric characters
DCMA INPUT F1
UNITS:
μ
A
Range: six alphanumeric characters
DCMA INPUT F1
RANGE: 0 to -1 mA
Range: 0 to –1 mA, 0 to +1 mA, –1 to +1 mA, 0 to 5
mA, 0 to 10mA, 0 to 20 mA, 4 to 20 m
DCMA INPUT F1 MIN
VALUE: 0.000
Range: –9999.999 to +9999.999 in steps of 0.001
DCMA INPUT F1 MAX
VALUE: 0.000
Range: –9999.999 to +9999.999 in steps of 0.001
The N60 is provided with optional DCmA capability. This feature is specified as an option at the time of
ordering. See the Order Codes section in chapter 2 for details.