5-20
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Table 5-5: Security alarm settings
CyberSentry settings through the front panel
SETTINGS
PRODUCT SETUP
SECURITY
Firmware Lock
(via Lock Relay)
Indicates if the device receives firmware
upgrades. If Enabled and the firmware
upgrade attempt is made, the device denies
the upgrade and displays an error message
that the lock is set. On each firmware upgrade,
this setting goes back to the default.
The Lock Relay setting blocks settings and
firmware updates.
Disabled
Enabled
Enabled
-
Administrator
Factory Service
Mode
When enabled, the device can go into factory
service mode. To enable, Supervisor
authentication is necessary.
Disabled
Enabled
Disabled
-
Supervisor
(Administrator
when Supervisor
is disabled)
Restore to Defaults Sets the device to factory defaults
No
Yes
No
-
Administrator
Supervisor Role
When enabled, the Supervisor role is active. To
enable, Administrator authentication is
necessary. When disabled, the Supervisor role
is inactive. To disable, Supervisor
authentication is necessary.
Disabled
Enabled
Enabled
-
Administrator to
enable and
Supervisor to
disable
RADIUS user names Ensures that RADIUS user names are not the
same as local/device role names
See RADIUS
server
documents
See
RADIUS
server
document
s
-
Administrator
Password
Local/device roles except for Observer are
password-protected. All RADIUS users are
password-protected.
See the
Password
Requirements
section earlier
in this chapter
See the
following
password
section for
requireme
nts
Change
Me1#
Text
The specified
role and
Administrator,
except for
Supervisor,
where it is only
itself
Setting name
Description / Details
Min
Max
Default
Units
Minimum
permissions
Failed
Authentications
A threshold number indicating when an alarm
is set off to indicate too many failed
authentication attempts
0
(disabled)
99
3
-
Administrator
Firmware Lock
A value indicating if the device can receive a
firmware upgrade. If Enabled and a firmware
upgrade attempt is made, the device alarm
activates. If Disabled, the device alarm does not
activate. On each firmware upgrade this setting
goes back to the default.
Disabled Enabled Enabled
-
Administrator
Settings Lock
A value indicating if the device can accept any
settings changes. If Enabled and a settings
change attempt is made, the device alarm
activates. If Disabled, the device alarm does not
activate.
Disabled Enabled Enabled
-
Supervisor
(Administrator if
Supervisor has
been disabled)
SECURITY
LOGIN:
None
Range: Administrator, Engineer, Supervisor,
Operator, Factory (for factory use only), None
CHANGE LOCAL
PASSWORDS
SESSION
SETTINGS
Setting name
Description
Minimum
Maximum Default
Units Minimum
permission