CHAPTER 2: INSTALL ATION/CONFIGURATION
2.48
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
For EntelliPro ES3 types:
Input 99 is mapped to forward contactor 1 feedback
- active high
Input 98 is mapped to reverse contactor 2 feedback
- active low
Input 97 is mapped to by-pass contactor feedback
- active high
Input 96 is mapped to up-to-speed feedback
- active high
Input 95 is mapped to emergency circuit
- active low
Input 94 is mapped to starter fault
- active low
Input 93 is mapped to safety circuit
- active low
Output 41 is mapped to forward contactor 1
Output 43 is mapped by-pass contactor
Output 45 is mapped to reverse contactor 2
For EntelliPro ES5 types:
Input 99 is mapped to forward contactor 1 feedback
- active high
Input 98 is mapped to reverse contactor 2 feedback
- active high
Input 97 is mapped to by-pass contactor feedback
- active high
Input 96 is mapped to up-to-speed feedback
- active high
Input 95 is mapped to starter fault feedback
- active low
Input 94 is mapped to main circuit feedback
- active low
Input 93 is mapped to control circuit feedback
- active low
Input 11 is mapped to command OFF
- active low
Input 12 is mapped to command forward ON1
- active high
Input 13 is mapped to command reverse ON2
- active high
Input 14 is mapped to external fault 1
- active high
Input 15 is mapped to external fault 2
- active low
Input 16 is mapped to emergency stop
- active low
Input 17 is mapped to safety circuit
- active low
Input 18 is mapped to mode switch local
- active high
Input 19 is mapped to mode switch remote
- active high
Output 41 is mapped to forward contactor 1
Output 43 is mapped to reverse contactor 2
Output 45 is mapped to by-pass contactor
Output 22 is mapped to ATEX redundancy contactor
Output 23 is mapped to ON1/ON2 command (start)
Output 24 is mapped to reset
Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority)
Output 26 is mapped to failure