EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL
4.27
CHAPTER 4: COMMUNICATION
Holding
Register
Modbus
Size
Variable
Description
Min
Max
Step
Units
Scale
Format
Default
130
16 bit
Configuration Bits
bit 0 - Class1BusFailureDetection
bit 1 - ModbusBusFailureDetection
bit 2 - ActivateThermistorLineBreakAnd
ShortedSupervision
bit 3 - ActivateDrawerPositionSupervision
bit 4 -
bit 5 - Remote Source Control OFF
0 - disabled
1- enabled
0 - disabled
1- enabled
0 - disabled
1- enabled
0 - disabled
1- enabled
If set to 1; Switch is set to LOCAL but and OFF
command from Remote source is accepted
0
127
Unsigned
Integer
5
132
16 bit
Firmware Version
Read only
Definition:
Firmware Version “000.000” => “HigherByte.
LowerByte”
Unsigned
Integer
0x01
134
16 bit
Free Logic Version[0 & 1]
Read only
0
135
16 bit
Free Logic Version[2 & 3]
Read only
0
136
16 bit
Free Logic Version[4 & 5]
Read only
0
162
16 bit
Serial Number[0 & 1]
Serial Number
Unsigned
Integer
163
16 bit
Serial Number[2 & 3]
164
16 bit
Serial Number[4 & 5]
165
16 bit
Serial Number[6 & 7]
166
16 bit
Serial Number[8 & 9]
167
16 bit
Serial Number[10 & 11]
169
170
32 bit
Operating Hour
Hour of operation
0
4294967296
1
Hour
Unsigned
Integer
171
172
32 bit
Motor Start Counter
Number of Motor Start
0
4294967296
1
Unsigned
Integer
173
174
32 bit
Switch Counter[0]
Number of operation of motor contactor 41
0
4294967296
1
Unsigned
Integer
175
176
32 bit
Switch Counter[1]
Number of operation of motor contactor 42
0
4294967296
1
Unsigned
Integer
177
178
32 bit
Switch Counter[2]
Number of operation of motor contactor 43
0
4294967296
1
Unsigned
Integer
179
180
32 bit
Switch Counter[3]
Number of operation oof motor contactor 45.
Mainly use on start-delta reverse typical
0
4294967296
1
Unsigned
Integer
181
16 bit
Thermal overloaf trip Counter
Thermal Overload Trip Counter
0
65536
1
Unsigned
Integer
182
16 bit
Thermistor Trip Counter
Thermistor Trip Counter
0
65536
1
Unsigned
Integer
183
16 bit
Ground Fault Sum trip Counter
Ground Fault Sum trip Counter
0
65536
1
Unsigned
Integer
184
185
32 bit
Non-Operation Hour
Hour of non-operation - motor stopped
0
65536
0
Hour
Unsigned
Integer
194
16 bit
Digital Output - Signal Relay 23
See Digital Output 0 for configuration and
setting (Holding register 126)
1
71
1
Unsigned
Integer
5
195
16 bit
DigitalOutput - Signal Relay 24
See Digital Output 0 for configuration and
setting (Holding register 126)
1
71
1
Unsigned
Integer
5
196
16 bit
DigitalOutput - Signal Relay 25
See Digital Output 0 for configuration and
setting (Holding register 126)
1
71
1
Unsigned
Integer
5
197
16 bit
DigitalOutput - Signal Relay 26
See Digital Output 0 for configuration and
setting (Holding register 126)
1
71
1
Unsigned
Integer
5
237
16 bit
ESS-type name[0 & 1]
Read Only
Catalog Number
Unsigned
Integer
238
16 bit
EntelliPro ES
-type name[2 & 3]
239
16 bit
E
ntelliPro ES
-type name[4 & 5]
240
16 bit
E
ntelliPro ES
-type name[6 & 7]
241
16 bit
E
ntelliPro ES
-type name[8 & 9]
242
16 bit
E
ntelliPro ES
-type name[10 & 11]
243
16 bit
E
ntelliPro ES
-type name[12 & 13]
244
16 bit
E
ntelliPro E
S-type name[14 & 15]
245
16 bit
E
ntelliPro E
S-type name[16 & 17]
246
16 bit
E
ntelliPro E
S-type name[18 & 19]
247
16 bit
E
ntelliPro E
S-type name[20 & 21]