1.2.4 Output specifications
4 - 20 mA Output
Accuracy...................................................................................±1% from displayed RMS
Motor Contact Relays
Configuration..........................................................................electromechanical SPST
Contact material ...................................................................silver alloy
Operate time...........................................................................10ms
Minimum contact load .......................................................10mA at 5Vdc
Continuous current ..............................................................5A at 240Vac
/ 30Vdc
Resistive load capacity
Maximum switched power ...............................................150W or 1250VA
Maximum switched current .............................................5A
Maximum switched voltage.............................................150Vdc or 250Vac
Life expectancy
Mechanical ..............................................................................20 million operations
Electrical ..................................................................................100,000 operations at 5A, 30Vdc or 250Vac
Application category (for AC-15 and DC-13) ............5A/240VA – AC-15
2.5A / 24Vdc – DC-13
According to IEC-60947-5-1
Normal and Abnormal Conditions
A7DQS or gl 10Amps fuses required
Signal Relays
Configuration..........................................................................electromechanical SPST
Contact material ...................................................................silver alloy
Operate time...........................................................................10ms
Minimum contact load .......................................................10mA at 5Vdc
Continuous current ..............................................................3A at240Vac
Resistive load capacity
Maximum switched current .............................................3A
Maximum switched voltage.............................................150Vdc or 250Vac
Life expectancy
Mechanical ..............................................................................20 million operations