CHAPTER 2: INSTALL ATION/CONFIGURATION
EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL
2.53
CAUTION:
EntelliPro ES should not be used as a means to provide instantaneous breaker protection.
If the default configuration and the breaker typical are selected in the WinESG parameterization/information panel
shown in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to
0x8,the inputs and outputs are mapped as below:
For EntelliPro ES3 types:
Input 99 is mapped to Breaker ON feedback
- active high
Input 98 is mapped to Breaker ready to switch ON feedback - active high
Input 97 is mapped to breaker charged feedback
- active high
Input 96 is mapped to main circuit feedback
- active low
Input 95 is mapped to breaker-tripped feedback
- active low
Input 94 is mapped to external fault 1
- active low
Input 93 is mapped to safety circuit
- active low
Output 41 is mapped to breaker ON
Output 43 is mapped to breaker OFF
Output 45 is mapped to reset
For EntelliPro ES5 types:
Input 99 is mapped to breaker ON feedback
- active high
Input 98 is mapped to breaker ready to switch ON feedback - active high
Input 97 is mapped to breaker charged feedback
- active high
Input 96 is mapped to external fault 1
- active low
Input 95 is mapped to breaker-tripped feedback
- active low
Input 94 is mapped to main circuit feedback
- active low
Input 93 is mapped to control circuit feedback
- active low
Input 11 is mapped to command OFF
- active low
Input 12 is mapped to command ON
- active high
Input 13 is mapped to reset alarm
- active high
Input 14 is mapped to external fault 1
- active high
Input 15 is mapped to external fault 2
- active low
Input 16 is mapped to emergency stop
- active low
Input 17 is mapped to safety circuit
- active low
Input 18 is mapped to mode switch local
- active high
Input 19 is mapped to mode switch remote
- active high