5.3.2.5 Parameterization Timer panel
Timer panel – The timer panel provide
s
a means for setting the 16 timers available on EntelliPro ES. The timers can be
adjusted within the range of 0.1 to 6553.5 seconds.
Refer to Figure 5-11 for the WinESG parameterization timer panel.
Figure 5-11-: WinESG parameterization timer panel
Contactor feedback time:
fault or warning is indicated if contactor feedback (current or
contactor) is not received within this time.
Motor start time:
fault or warning is indicated if a current is above the start phase
threshold for the set amount of time.
Modbus failure OFF/ON delay time:
fault or warning is indicated if a Modbus failure exists after this
time expires. Modbus timeout time must be set in Modbus
register 59.
Current feedback time:
fault or warning is indicated if a current is below 0.2 * Ir for the
set amount of time after a start.
Motor ON direction switch over time:
use mainly on two-speed motor. Transition from one speed to
the other will only occur after this time expires.
Class 1 failure OFF/ON delay time:
fault or warning is indicated if a Profibus class 1 failure exist
s
after
this time expires.
Over current delay time:
fault or warning is indicated if a current is above over current
threshold for the set amount of time.