4.26
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: COMMUNICATION
Holding
Register
Modbus
Size
Variable
Description
Min
Max
Step
Units
Scale
Format
Default
126
16 bit
Digital Output - Motor Relay 41
Note:
One of the three motor contact relay output
must be mapped as a contactor (value 1
thru 5).
When any motor contact relay is mapped as
a contact then the rest of the output relays
can be treated as a signal output and set to
any value.
Signal output can be dual mapped (first byte
mapped to operation1, and 2nd byte mapped
to a different operation)
Example of mapping output 3 as a signal
output relay
Identification Feedback Status = 23 (first
byte)
Main Contactor 2 Feedback Status
Flashing = 38 (second byte)
Convert 3823 to HEX = 0x0EEF.
Convert 0x0EEF to decimal - 3823
Place 3823 in the output 3 register
Note: second byte has the highest priority
when both are present
1 = Main Contactor 1 / Breaker ON / Slow
Contactor
2 = Main Contactor 2 / Breaker OFF / Fast
Contactor
3 = Start Contactor 3 / by pass Connector
4 = Delta Contactor 4
5 = Redundancy Contactor
6 = Main Contactor 1 Feedback Status
7 = Main Contactor 2 Feedback Status
8 = ESS_DP_Parameter_Mode
9 = Switch_Protected_Status
10 = Start_Attempt_Status
11 = Drawer_Ready_Status
12 = General Warning Status
13 = General Fault Status
14 = Safety Circuitry Status
15 = Local Switch Status
16 = Remote Switch Status
17 = Drawer test Mode Status
18 = Drawer operation Mode Status
19 = Limit Switch 1 Status
20 = Limit Switch 2 Status
21 = General Device Error Status
22 = Identification Feedback Status
23 = Class1 Failure
24 = Modbus Failure
25 = By Pass Contactor Switched ON Status
26 = Switching 1 progress Status
27 = Switching 2 progress Status
28 = Breaker Tripped2 Status
29 = Charger Status
30 = Torque Switching 1 Status
31 = Torque Switching 2 Status
32 = Start Phase Status
33 = Run Phase Status
34 = Thermistore Line Broken Status
35 = Thermistor Line Shorted Status
36 = Main Contactor 1 Feedback Status
37 = Main Contactor 2 Feedback Status
Flashing
38 = ESS_DP_Parameter_mode
39 = Switch_protected_Status Flashing
40 = Start_Attempt_Status Flashing,
41 = D
rawer
_R
eady
_Status Flashing,
42 = General Warning Status Flashing
43 = General Fault Status Flashing
44 = Safety Circuitry Status Flashing
45 = Local Switch Status Flashing
46 = Remote Switch Status Flashing
47 = Drawer test Mode Status Flashing
48 = Drawer operation Mode Status Flashing
49 = Limit Switch 1 Status Flashing
50 = Limit Switch 2 Status Flashing
51 = General Device Error Status Flashing
52 = Identification Feedback Status Flashing
53 = Class1 Failure Flashing
54 = Modbus Failure Flashing
55 = By Pass Contactor Switched ON Status
Flashing
56 = Switching 1 progress Status Flashing
57 = Switching 2 progress Status Flashing
58 = Breaker Tripped2 Status Flashing
59 = Charger Status Flashing
60 = Torque Switching 1 Status Flashing
61 = Torque Switching 2 Status Flashing
62 = Start Phase Status Flashing
63 = Run Phase Status Flashing
64 = Thermistore Line Broken Status Flashing
65 = Thermistor Line Shorted Status Flashing
66 = DIGITALOUTPUT4 / Soft Stop Relay
67 = DIGITALOUTPUT5 / Soft Start External
Fault
68 = Digital Output 6,
69 = Digital Output 7
70 = Digital Output 8
1
71
1
Unsigned
Integer
9
127
16 bit
Digital Output - Motor Relay 43
See Digital Output 0 for configuration and
setting (Holding register 126)
1
71
1
Unsigned
Integer
7
128
16 bit
Digital Output - Motor Relay 45
See Digital Output 0 for configuration and
setting (Holding register 126)
1
71
1
Unsigned
Integer
7
129
16 bit
Digital Output - Signal Relay 22
See Digital Output 0 for configuration and
setting (Holding register 126)
1
71
1
Unsigned
Integer
7