EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL
4.19
CHAPTER 4: COMMUNICATION
Holding
Register
Modbus
Size
Variable
Description
Min
Max
Step
Units
Scale
Format
Default
56
1
16 bit
Current Unbalance/Loss Delay
0-Disable
0
15
1
sec
Unsigned
Integer
1
57
16 bit
Analog RMS value time interval
Time interval between analog value log
samples
Example: If set to 60 - every 60 secs a
sample is recorded
1
60
1
sec
Unsigned
Integer
1
58
16 bit
Analog RMS Value Trigger
Bit0, Bit1, Bit2 - Event to stop storage
0 - Disable
1 - Trip
2 - Warning
3 - Switch ON
4 - Switch OFF
5 - Manual
Bit 3 -
0 - 3/4 pre and 1/4 post trigger data
1 - 1/4 pre and 3/4 post trigger data
Bit 4 - Reserved
Bit 5 - Reserved
Bit 6 - Reserved
Bit 7 - Reserved
Trigger mechanism
Number of pre and post trigger samples
recorded.
0
15
1
Unsigned
Integer
0
59
16 bit
Modbus Timeout Timer
Time allowed between Modbus messages until
Modbus error is generated
1
120
1
sec
Unsigned
Integer
62
16 bit
Special Functions
Bit0 = Default Configuration
Bit1 = Disable alarm underload current
Bit2 - Disable alarm overload current
Bit3-4 Parameterization configuration
Bit 5 - Ignore Phase loss during start phase
Bit 6 - Ignore earth fault during start phase
Bit 7 - Ignore Unbalance load during start
phase
Bit 8 to 11- Typical selection
Bit 12 to 15 - Control mode variant selection
If set to 1 - typical and control mode default
configuration will be used.
0 0 - parameterization allowed via Profibus DP
only when motor is in stop condition
0 1 - parameterization allowed via Profibus DP
while motor is at any state.
1 0 - parameterization allowed via Profibus
DP when draw out position is not in test or
operation mode
11 - parameterization allowed via Profibus
DP when the operation mode is not Remote
or Local. Note: the Modbus operation mode
selection is done using function code 05 -
commands 10 or 11
1 - Ignored phase loss during start-up
0 - Do not ignore
1 - Ignored earth fault during start-up
0 - Do not ignore
1 - Ignored current unbalance during start-up
0 - Do not ignore
0xX0XX = DOL
0xX1XX = DOL Reverse
0xX2XX = Start Delta
0xX3XX = Start Delta Reverse
0xX4XX = Soft Starter
0xX5XX = Soft Starter Reverse
0xX6XX = Dahlander
0xX7XX = Pole Change Starter
0xX8XX = Breaker Control
0xX9XX = Solenoid Valve
0xXAXX = Actuator
0xXBXX = Custom Logic
1 - 6 - Refer to Chapter 2, Section 2.4.2
0
255
1
Unsigned
Integer
1: If ATEX is selected, the current unbalance/loss delay is automatically set to trip immediately.