CHAPTER 2: INSTALL ATION/CONFIGURATION
2.80
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
For EntelliPro ES3 types:
Input 99 is mapped to contactor 1 feedback
- active high
Input 98 is mapped to contactor 2 feedback
- active low
Input 97 is mapped to limit switch 1 reached
- active low
Input 96 is mapped to limit switch 2 reached
- active low
Input 95 is mapped to emergency stop
- active low
Input 94 is mapped to main circuit feedback
- active high
Input 93 is mapped to safety circuit
- active low
Output 41 is mapped to contactor 1
Output 43 is mapped to contactor 2
Output 45 is mapped to failure
For EntelliPro ES5 types:
Input 99 is mapped to contactor 1 feedback
- active high
Input 98 is mapped to contactor 2 feedback
- active high
Input 97 is mapped to external supervision 1
- active high
Input 96 is mapped to mode switch local
- active high
Input 95 is mapped to mode switch remote
- active high
Input 94 is mapped to main circuit feedback
- active low
Input 93 is mapped to control circuit feedback
- active low
Input 11 is mapped to command OFF
- active low
Input 12 is mapped to command ON1
- active high
Input 13 is mapped to command ON2
- active high
Input 14 is mapped to torque switch 1 feedback
- active low
Input 15 is mapped to torque switch 2 feedback
- active low
Input 16 is mapped to emergency stop
- active low
Input 17 is mapped to safety circuit
- active low
Input 18 is mapped to limit switch 1 feedback
- active low
Input 19 is mapped to limit switch 2 feedback
- active low
Output 41 is mapped to contactor 1
Output 43 is mapped to contactor 2
Output 45 is mapped to ATEX redundancy contactor
Output 22 is mapped to local control
Output 23 is mapped to ON1 – relay flashing
Output 24 is mapped to ON2 – relay flashing
Output 25 is mapped to drawer ready switch (high priority) and identification – relay flashing (low priority)
Output 26 is mapped to failure
NOTE:
If default configuration box is left un-checked, the user will have the ability to change the mapping and other
parameters.