CHAPTER 2: INSTALL ATION/CONFIGURATION
EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL
2.83
Tables below show the default configuration for all typicals.
Motor Starter Standard Configuration
EntelliPro ES3
Full-voltage
non-
reversing
Full-voltage
reversing
Star-delta
non-
reversing
Star-delta
reversing
Softstarter
Softstarter
reversing
Breaker
Dahlander
Pole-
changer
Actuator
Solenoid
valve
Feedback via contact Activated
Activated
Activated
Activated
N/A
Activated
Activated
Activated
Activated
Activated
Activated
Activated
Feedback via current Activated
Activated
Activated
Activated
N/A
Activated
Activated
N/A
Activated
Activated
Activated
N/A
Direct Switch over without OFF command
N/A
Deactivated
N/A
N/A
N/A
Deactivated
N/A
Activated
Activated
Deactivated
N/A
Current depending YD Switch Over
N/A
N/A
Activated
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Soft Stop Timer
N/A
N/A
N/A
N/A
Deactivated
Deactivated
N/A
N/A
N/A
N/A
N/A
Bypass Control
N/A
N/A
N/A
N/A
Activated
Activated
N/A
N/A
N/A
N/A
N/A
External Soft Starter Fault
N/A
N/A
N/A
N/A
Activated
Activated
N/A
N/A
N/A
N/A
N/A
MCCB Tripped 2 Configuration (Alarm or
No-Alarm)
N/A
N/A
N/A
N/A
N/A
N/A
no alarm
N/A
N/A
N/A
N/A
Breaker Trip Reset from EntelliPro ES
N/A
N/A
N/A
N/A
N/A
N/A
Activated
N/A
N/A
N/A
N/A
MCCB Feedback
N/A
N/A
N/A
N/A
N/A
N/A
Activated
N/A
N/A
N/A
N/A
Torque Switch
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Disable
N/A
Switch OFF at Limit Switch
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Activated
N/A
Switch OFF at Current Threshold
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Deactivated
N/A
Switch OFF at Torque Switch
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Deactivated
N/A
Enable Modbus RTU Control
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable Profibus DP Class 2 Control
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Enable Hardwired Control
Disable
Disable
Disable
N/A
Disable
Disable
Disable
Disable
Disable
Disable
Disable
bit 1 - Class1 n bit 0r (n+1) bit
n bit
n bit
n bit
N/A
n bit
n bit
n bit
n bit
n bit
n bit
n bit
bit 2 - Level/Edge
Level
Level
Level
N/A
Level
Level
Level
Level
Level
Level
Level
bit 3 - Inverted OFF / Non-Inverted OFF
non
non
non
N/A
non
non
non
non
non
non
non
bit 1 - Hardwire n bit 0r (n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
N/A
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
(n+1) bit
bit 2 - Hardwire Level/Edge
Edge
Edge
Edge
N/A
Edge
Edge
Edge
Edge
Edge
Edge
Edge
Thermistor Line Broken/Shorted Supervision.
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Drawer Position Supervision
Deactivated
Deactivated
Deactivated
N/A
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Drawer Position 1 bit Modus / 2 bit Modbus
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Modbus Failure Detection
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
ATEX Activated
Deactivated
Deactivated
Deactivated
N/A
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
bit 5 - Remote OFF always valid
Deactivated
Deactivated
Deactivated
N/A
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
Deactivated
bit 6 - Block Local Switch ON
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Alarm Setting
Overload
Enable
Enable
Enable
N/A
Enable
Enable
Disable
Enable
Enable
Enable
Enable
Phase Loss
Enable
Enable
Enable
N/A
Enable
Enable
Disable
Enable
Enable
Enable
Disable
Ground Fault
Enable
Enable
Enable
N/A
Enable
Enable
Disable
Enable
Enable
Enable
Disable
Unbalance Load
Enable
Enable
Enable
N/A
Enable
Enable
Disable
Enable
Enable
Enable
Disable
Thermsitor
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Emergency Stop
Enable
Enable
Enable
N/A
Enable
Enable
Disable
Enable
Enable
Enable
Enable
Limit Switch
Disable
Disable
Disable
N/A
Disable
Disable
Disable
Disable
Disable
Enable
Enable
Safety Circuit
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Main Circuit
Enable
Enable
Enable
N/A
Enable
Disable
Enable
Enable
Enable
Enable
Enable
Control Circuit
Enable
Enable
Disable
N/A
Disable
Disable
Disable
Disable
Enable
Disable
Disable
Switch Position
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Underload Current
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Overload Current
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Enable
Enable
External Supervisory
Enable
Enable
Enable
N/A
Enable
Enable
Enable
Enable
Enable
Disable
Enable
Long Start Time
Enable
Enable
Enable
N/A
Enable Enable
Enable
e
Ena
ble
En
able
Enable
i
Di
sabl
e
Input Mapping
Input 99 Mapping
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
N/A
Contactor 1
Feedback
Contactor 1
Feedback
MCCB ON
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Contactor 1
Feedback
Input 99 High/low Activation
Active High
Active High
Active High
N/A
Active High
Active High
Active High
Active High
Active High
Active High
Active High
Input 98 Mapping
External
Supervision
Contactor 2
Feedback
Contactor 2
Feedback
N/A
Main Circuit
Feedback
Contactor 2
Feedback
Breaker
Ready to
Switch ON
Contactor 2
Feedback
Contactor 2
Feedback
Contactor 2
Feedback
Main Circuit
Feedback
Input 98 High/Low activation
Active Low
Active High
Active High
N/A
Active Low
Active High
Active High
Active High
Active High
Active High
Active Low