CHAPTER 2: INSTALL ATION/CONFIGURATION
EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL
2.23
For EntelliPro ES3 types:
Input 99 is mapped to contactor 1 feedback
- active high
Input 98 is mapped to external supervision
- active low.
Input 97 is mapped to control circuit feedback
- active low
Input 96 is mapped to main circuit feedback
- active low
Input 95 is mapped to emergency stop
- active low
Input 94 is mapped to external supervision
- active high
Input 93 is mapped to safety circuit
- active low
Output 41 is mapped to contactor 1
Output 43 is mapped to ON1 feedback
Output 45 is mapped to failure
For EntelliPro ES5 types:
Input 99 is mapped to contactor 1 feedback
- active high
Input 98
- not used
Input 97 is mapped to reset alarm
- active high
Input 96 is mapped to drawer in test mode
- active high
Input 95 is mapped to drawer in operation mode
- active high
Input 94 is mapped to main circuit feedback
- active low
Input 93 is mapped to control circuit
- active low
Input 11 is mapped to command OFF
- active low
Input 12 is mapped to command ON
- active high
Input 13
- not used
Input 14 is mapped to external fault
- active high
Input 15 is mapped to external supervision
- active low
Input 16 is mapped to emergency stop
- active low
Input 17 is mapped to safety circuit
- active low
Input 18 is mapped to mode switch local
- active high
Input 19 is mapped to mode switch remote
- active high
Output 41 is mapped to contactor 1
Output 43 is mapped to ATEX redundancy contactor
Output 45 is mapped to warning (high priority) and failure - relay flashing (low priority)
Output 22 is mapped to local control
Output 23 is mapped to ON1 feedback
Output 24 is mapped to warning
Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority)
Output 26 is mapped to failure