CHAPTER 2: INSTALL ATION/CONFIGURATION
2.84
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
Motor Starter Standard Configuration
EntelliPro ES3
Full-voltage
non-
reversing
Full-voltage
reversing
Star-delta
non-
reversing
Star-delta
reversing
Softstarter
Softstarter
reversing
Breaker
Dahlander
Pole-
changer
Actuator
Solenoid
valve
Input 97 Mapping
Control
Circuit
Feedback
Control
Circuit
Feedback
Contactor 3
Feedback
N/A
Bypass
Feedback
Bypass
Feedback
Breaker
Charged
Contactor 3
Feedback
Control
Circuit
Feedback
Limit Open
Feedback
Limit Open
Feedback
Input 97 High/low Activation
Active Low
Active Low
Active High
N/A
Active High
Active High
Active High
Active High
Active Low
Active Low
Active Low
Input 96 Mapping
Main Circuit
Feedback
Main Circuit
Feedback
Main Circuit
feedback
N/A
Up to Speed
Feedback
Up to Speed
Feedback
Main Circuit
Feedback
Main Circuit
Feedback
Main Circuit
Feedback
Limit Close
Feedback
Limit Close
Feedback
Input 96 High/low Activation
Active Low
Active Low
Active Low
N/A
Active High
Active High
Active Low
Active Low
Active Low
Active Low
Active Low
Input 95 Mapping
Emergency
Stop
Emergency
Stop
Emergency
Stop
N/A
Emergency
Stop
Emergency
Stop
Breaker
Tripped 2
Emergency
Stop
Emergency
Stop
Emergency
Stop
Emergency
Stop
Input 95 High/low Activation
Active Low
Active Low
Active Low
N/A
Active Low
Active Low
Active Low
Active Low
Active Low
Active Low
Active Low
Input 94 Mapping
External
Supervision
External
Supervision
External
Supervision
N/A
Starter Fault
Feedback
Starter Fault
Feedback
Tripped
External
Supervision
External
Supervision
External
Supervision
External
Supervision
Input 94 High/low Activation
Active High
Active High
Active High
N/A
Active Low
Active Low
Active Low
Active High
Active High
Active Low
Active High
Input 93 Mapping
Safety
Circuit
Safety
Circuit
Safety
Circuit
N/A
Safety
Circuit
Safety
Circuit
Safety
Circuit
Safety
Circuit
Safety
Circuit
Safety
Circuit
Safety
Circuit
Input 93 High/low Activation
Active Low
Active Low
Active Low
N/A
Active Low
Active Low
Active Low
Active Low
Active Low
Active Low
Active Low
Relay Output Mapping
First Function Relay 42 Mapping
Contactor 1
Contactor 1
Contactor 1
N/A
Contactor 1
Contactor 1
MCCB on
Contactor 1
Contactor 1
Contactor 1
Contactor 1
Second Function Relay 42 Mapping
None
None
None
N/A
None
None
None
None
None
None
None
First Function Relay 43 Mapping
ON 1
Feedback
Contactor 2
Contactor D
N/A
Bypass
Bypass
MCCB off
Contactor 2
Contactor 2
Contactor 2
ON 1
Feedback
Second Function Relay 43 Mapping
None
None
None
N/A
None
None
None
None
None
None
None
First Function Relay 45 Mapping
Failure
Failure
Contactor Y
N/A
Reset
Left
Reset
Contactor Y
Failure
Failure
Failure
Second Function Relay 45 Mapping
None
None
None
N/A
None
None
None
None
None
None
None
First Function Relay 22 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Second Function Relay 22 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
First Function Relay 23 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Second Function Relay 23 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
First Function Relay 24 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Second Function Relay 24 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
First Function Relay 25 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Second Function Relay 25 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
First Function Relay 26 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Second Function Relay 26 Mapping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Table 2-6: EntelliPro ES3 Motor Starter Configuration