CHAPTER 5: WinESG
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
5.1
4
Successful writing is displayed in the message area, shown in illustration E. The writing can be invalid, if there is no
communication, or the device is not ready for parameterization or one or more parameters are out of limit.
Illustration F shows the Place Identifier, which allows the user to indentify the unit in the system. Each text can be 20
characters long.
Illustration G shows the Device Identifier.
Device Type:
catalog number of the device.
Typical:
selection of the typical. Refer to section 2.3 for additional information
.
If Custom Logic is selelected EntelliPro power must be cycled.
Control Mode:
selection of control variant. Refer to section
.
2.2.2 for additional information
Default Configuration: allows the selection of the 6 pre-defined control type, and it configures the
device with a set of factory pre-programmed parameters. These pre-
programmed parameters can be changed if default configuration is
unselected. Refer to section 2.2.2 for additional information
NOTE:
If the drive typical is set to “Fully free logic”, the Profibus Class 2 data interface of the free logic must follow the
Illustration H shows the Hardware Overview, which provides power supply, number of inputs and outputs ratings.
CAUTION:
EntelliPro ES standard, otherwise the data in the WinESG might be incorrect.
Writing parameters to the device changes the protection and control behavior of the EntelliPro ES, and can
result in operating the contactor(s).
5.3.2.2 Parameterization Device Setting panel
The device setting panel provides a method to configure the current transformer, motor load, overload trip class and
cooling factor, ground fault threshold and time delay, current threshold, analog output, analog output limit value,
current threshold, number of phase
s
, phase unbalance delay, analog value interval, stop analog storage event, pre-post
trigger values. Refer to figure 5-8 for the WinESG parameterization device setting panel.