EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL
1.13
1.2.5 Power supply specifications
This section lists the specifications for the power supply. The power consumptions of the EntelliPro
modules are listed in Table 1-3.
Nominal.....................................................................................24Vdc (24Vdc version)
/140mA (max)
110/240Vac (120/240Vac version)/60mA (max)
Range.........................................................................................19–28.8Vdc (24Vdc version)
77–264Vac (110/240Vac version)
Ride-through...........................................................................30ms
1.2.6 Communication specifications
Profibus
Port..............................................................................................opto-isolated
Modes ........................................................................................DP V1 slave, up to 12Mbps
Connector ................................................................................9-pin D connector
Standard ...................................................................................IEC 61158
Installation ...............................................................................PI installation guidelines
Modbus RTU over RS485
Port...............................................................................................opto-isolated
Baud rates ...............................................................................up to 19.2kbps (Modbus
Protocol .....................................................................................half-duplex