CHAPTER 2: INSTALL ATION/CONFIGURATION
2.10
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
2.2 Motor Control Configuration
This se
ction
is split into two parts; one for an expert integrator requiring a full knowledge of all
parameters and configuration and the other requiring minimal knowledge to configure the EntelliPro ES
.
For the expert user, refer to section 2.2.1. For non-expert user, refer to sections 2.2.2.
2.2.1 Motor Control Detailed Configuration
The EntelliPro ES can control the motor (start, stop, reset …) by four means: Profibus class 1, which can be
PLC or other automation systems, Modbus RTU master, which can be the EntelliPro CP or other Modbus
RTU base system, Hardwire and WinESG.
The first step in the configuration is to assign the four sources (Profibus class1, CP/Modbus RTU, Hardwire,
WinESG) as locals or remote. This is done in WinESG parameterization/control panel shown in the illustration
below or Modbus function code 6 register 115. If a source is not assigned as remote, it automatically becomes
a local source if enabled by checking the box to the right of the source. Only one remote source can be
selected.
NOTE:
If Profibus Class 1 is enabled, the remote source selection can only be set to Class 1.
In addition EntelliPro ES provides a “local-remote-off” switch which selects if locals or remote sources control
the motor ON/OFF operation.
NOTE:
Only one source can control the switch.
The following sources can be configured as the controller of the “local-remote-off ” switch
configuration:
Profibus Class 1
The “local-remote-off ” switch can only be configured over
CP / Modbus RTU
The “local-remote-off” switch can only be configured
over Entellipro CP / Modbus RTU module or other
Modbus masters modules.
Hardwire
The “local-remote-off” switch can only be configured with
hardwired input. Switch must be connected to the input
and the input mapped accordingly.
Profibus Class 1 master module.