CHAPTER 3: MOTOR PR OTECTION
3.16
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
When the auto-reset parameter is set to 1, the Auto-Reset is allowed after an overload trip occurred.
NOTE:
auto reset will NOT be allowed for 1 hour after the last trip.
When the auto-reset parameter is set to 2, 2 auto-Resets are allowed after an overload trip occurred.
NOTE:
auto reset will NOT be allowed for 1 hour after the second trip.
When the auto-reset parameter is set to 3, 3 auto-resets are allowed after an overload trip occurred.
NOTE:
auto reset will NOT be allowed for 1 hour after the third trip.
The auto-reset can be set to higher values if ATEX is disabled. For settings above 4, auto-
r
eset is always allowed.
NOTE:
If the EntelliPro ES is configured as an ATEX device, the n-times reset cannot be set to “always” auto- reset .