EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL
4.15
CHAPTER 4: COMMUNICATION
4.1.10.6 Function Code
14
H
Modbus Implementation: Read File Record
EntelliPro Implementation: Read Full Event and Analog Data
This command allows the master to read a file containing the full 255 events and analog RMS data. All Request
Data Lengths are provided in terms of number of bytes and all Record Lengths are provided in terms of registers.
Master Transmission
Bytes
Value
Slave Address
1
1 - 245
Function Code
1
0x14
Byte Count
1
0x07 to 0xF5
Reference Type
2
06
File Number
2
0x0001 (Read all 255 Events)
0x0002 (Read Current RMS)
Record Number
2
0x 0000 to 0x03E8
Register Length
2
0x0000 to 0 x 007B
Table 4-8: Function Code
14H
4.1.10.7 Function Code 1
5
H
Modbus Implementation: Write File Record EntelliPro Implementation: Write
“Custom” logic
This command allows the master to write a file containing the custom logic to the EntelliPro ES. This function code is
used to perform a file record write. All Request Data Lengths are provided in terms of number of bytes and all Record
Lengths are provided in terms of the number of 16-bit words.
Master Transmission
Bytes
Value
Slave Address
1
1 - 245
Function Code
1
0x15
Reference Type
1
06
File Number
2
0x03FF
Record Number
2
Record Number
2
Register Length
2 x N
Table 4.9 Function Code 1
5
H