CHAPTER 3: INSTALLATION
WIRING
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
3-21
3
Figure 3-19: RTD connections
3.3.7 RS232 faceplate port
A nine-pin RS232C serial port is located on the faceplate for programming with a computer. All that is required to use this
interface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is
shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port can be set, with a default of 115200 bps.
Figure 3-20: RS232 faceplate port connection
3.3.8 CPU communication ports
3.3.8.1 Overview
In addition to the faceplate RS232 port, there is a rear RS485 communication port.
Three-wire shielded cable
RTD terminals
Maximum total lead resistance:
25 ohms for Platinum RTDs
Route cable in separate conduit from
current carrying conductors
RTD
859736A1.CDR
RTD terminals
RTD
RTD
For RTD
RTD
SURGE
~1
~1 & ~2
~2
~8b
~1a
~1b
~2a
Hot
Hot
Return
Comp
Comp ~2c
~1c