![GE Digital Energy L60 Instruction Manual Download Page 250](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854250.webp)
5-120
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
BREAKER 1
Φ
A/3P CLOSED
— Selects an operand, usually a contact input connected to a breaker auxiliary position tracking
mechanism. This input is a normally-open 52/a status input to create a logic 1 when the breaker is closed. If the
BREAKER 1
MODE
setting is selected as
“
3-Pole,
”
this setting selects a single input as the operand used to track the breaker open or
closed position. If the mode is selected as
“
1-Pole,
”
the input mentioned is used to track phase A and the
BREAKER 1
Φ
B
and
BREAKER 1
Φ
C
settings select operands to track phases B and C, respectively.
BREAKER 1
Φ
A/3P OPND
— Selects an operand, usually a contact input, that is a normally-closed 52/b status input to create
a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the inverted
BREAKER 1 CLOSED
status
signal can be used.
BREAKER 1
Φ
B CLOSED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B closed position as outlined for phase A.
BREAKER 1
Φ
B OPENED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase B opened position as outlined for phase A.
BREAKER 1
Φ
C CLOSED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C closed position as outlined for phase A.
BREAKER 1
Φ
C OPENED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the breaker phase C opened position as outlined for phase A.
BREAKER 1 Toperate
— This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has expired, the
BREAKER 1 BAD STATUS
FlexLogic operand is asserted from alarm or blocking purposes.
BREAKER 1 EXT ALARM
— This setting selects an operand, usually an external contact input, connected to a breaker alarm
reporting contact.
BREAKER 1 ALARM DELAY
— This setting specifies the delay interval during which a disagreement of status among the three-
pole position tracking operands does not declare a pole disagreement. This allows for non-simultaneous operation of the
poles.
If single-pole tripping and reclosing is used, the breaker can trip unsymmetrically for faults. In this case, the minimum
alarm delay setting must exceed the maximum time required for fault clearing and reclosing by a suitable margin.
MANUAL CLOSE RECAL1 TIME
— This setting specifies the interval required to maintain setting changes in effect after an
operator has initiated a manual close command to operate a circuit breaker.
BREAKER 1 OUT OF SV
— Selects an operand indicating that breaker 1 is out-of-service.