5-176
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
5.6.4 Line pickup
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LINE PICKUP
The line pickup feature uses a combination of undercurrent and undervoltage to identify a line that has been de-energized
(line end open). Alternately assign a FlexLogic operand to the
TERMINAL OPEN
setting that specifies the terminal status.
Three instantaneous overcurrent elements are used to identify a previously de-energized line that has been closed onto a
fault. Faults other than close-in faults can be identified satisfactorily with the distance elements.
Co-ordination features are included to ensure satisfactory operation when high-speed automatic reclosure (AR) is
employed. The
AR CO-ORD DELAY
setting allows the overcurrent setting to be below the expected load current seen after
reclose. Co-ordination is achieved by all of the
LINE PICKP UV
elements resetting and blocking the trip path before the
AR
CO-ORD DELAY
times out. The
AR CO-ORD BYPASS
setting is normally enabled. It is disabled if high speed autoreclosure is
implemented.
The line pickup protection incorporates zone 1 extension capability. When the line is being re-energized from the local
terminal, pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser
issues a close command results in the
LINE PICKUP RCL TRIP
FlexLogic operand. For security, the overcurrent trip is
supervised by an undervoltage condition, which in turn is controlled by the
VT FUSE FAIL OP
operand with a 10 ms
coordination timer. If a trip from distance is not required, then it can be disabled with the
LINE PICKUP DISTANCE TRIP
setting.
Configure the
LINE PICKUP RCL TRIP
operand to perform a trip action if the intent is zone 1 extension.
LINE PICKUP
LINE PICKUP
FUNCTION: Disabled
Range: Disabled, Enabled
LINE PICKUP SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
PHASE IOC LINE
PICKUP: 1.000 pu
Range: 0.000 to 30.000 pu in steps of 0.001
LINE PICKUP UV PKP:
0.700 pu
Range: 0.000 to 3.000 pu in steps of 0.001
LINE END OPEN PICKUP
DELAY: 0.150 s
Range: 0.000 to 65.535 s in steps of 0.001
LINE END OPEN RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
LINE PICKUP OV PKP
DELAY: 0.040 s
Range: 0.000 to 65.535 s in steps of 0.001
AR CO-ORD BYPASS:
Enabled
Range: Disabled, Enabled
AR CO-ORD PICKUP
DELAY: 0.045 s
Range: 0.000 to 65.535 s in steps of 0.001
AR CO-ORD RESET
DELAY: 0.005 s
Range: 0.000 to 65.535 s in steps of 0.001
TERMINAL OPEN:
Off
Range: FlexLogic operand
AR ACCELERATE:
Off
Range: FlexLogic operand
LINE PICKUP DISTANCE
TRIP: Enabled
Range: Disabled, Enabled
LINE PICKUP BLOCK:
Off
Range: FlexLogic operand
LINE PICKUP
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
LINE PICKUP
EVENTS: Disabled
Range: Disabled, Enabled