CHAPTER 6: ACTUAL VALUES
METERING
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
6-17
6
This menu displays metered values for real, reactive, and apparent power, as well as power factor. The "SRC 1" text is
replaced by the name programmed by the user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL
SOURCES
).
When VTs are configured in wye, the L60 calculates power in each phase and three-phase power is measured as
S = V
A
x Î
A
+ V
B
x Î
B
+ V
C
x Î
C
Eq. 6-1
When VTs are configured in delta, the L60 does not calculate power in each phase and three-phase power is measured as
S = V
AB
x Î
A
+ V
CB
x Î
C
Eq. 6-2
where
S is the apparent power
V
A
, V
B
, V
C
, I
A
, I
B
, I
C
are phase voltage and phase current phasors
V
AB
and V
CB
are phase-to-phase voltage phasors
Î is the conjugate of I
6.3.2.7 Frequency metering
ACTUAL VALUES
METERING
SOURCE SRC 1
FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text is replaced by the name programmed by the
user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL SOURCES
).
SOURCE FREQUENCY
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP
POWER SYSTEM
settings). The signal used for frequency estimation is low-pass filtered. The final
frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
6.3.3 Synchrocheck
ACTUAL VALUES
METERING
SYNCHROCHECK
SYNCHROCHECK 1(4)
If a synchrocheck function setting is "Disabled," the corresponding actual values menu item does not display.
6.3.4 Tracking frequency
ACTUAL VALUES
METERING
TRACKING FREQUENCY
The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
setting in the
SETTINGS
SYSTEM SETUP
POWER SYSTEM
menu. See the Power
System section of chapter 5 for details.
FREQUENCY
SRC 1
SRC 1 FREQUENCY:
0.00 Hz
SYNCHROCHECK 1
SYNCHROCHECK 1 DELTA
VOLT: 0.000 V
SYNCHROCHECK 1 DELTA
PHASE: 0.0°
SYNCHROCHECK 1 DELTA
FREQ: 0.00 Hz
TRACKING FREQUENCY
TRACKING FREQUENCY
60.00 Hz