![GE Digital Energy L60 Instruction Manual Download Page 161](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854161.webp)
CHAPTER 5: SETTINGS
PRODUCT SETUP
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-31
5
Multiple LANS, no redundancy
The following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) is
connected, access to the public network on LAN2, to which port 2 (P2) is connected, and communications with SCADA on
LAN3, to which port 3 (P3) is connected. There is no redundancy.
Figure 5-7: Multiple LANS, no redundancy
5.3.4.4 Network
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the
routing settings.
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
NETWORK 1(3)
NETWORK PORT 1
PRT1 IP ADDRESS:
127.0.0.1
Range: standard IPV4 address format
PRT1 SUBNET IP MASK:
255.0.0.0
Range: standard IPV4 address format
NETWORK PORT 2
PRT2 IP ADDRESS:
127.0.0.1
Range: standard IPV4 address format
PRT2 SUBNET IP MASK:
255.0.0.0
Range: standard IPV4 address format
PRT2 REDUNDANCY:
None
Range: None, Failover, PRP
Range if no PRP license: None, Failover
PRT2 PRP MCST ADDR:
01-15-4E-00-01-00
Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF
NETWORK PORT 3
PRT3 IP ADDRESS:
127.0.0.1
Range: standard IPV4 address format
PRT3 SUBNET IP MASK:
255.0.0.0
Range: standard IPV4 address format
EnerVista Software
ML3000
Public Network
SCADA
UR
P1
IP1/
MAC1
P2
IP2/
MAC2
ML3000
ML3000
LAN1
LAN2
LAN3
P3
IP3/
MAC3
859710A2.vsd