CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-277
5
Example 2: Breaker trip circuit integrity monitoring
If it is required to monitor the trip circuit continuously, independent of the breaker position (open or closed), a method to
maintain the monitoring current flow through the trip circuit when the breaker is open must be provided (as shown in the
following figure). This can be achieved by connecting a suitable resistor (see figure) across the auxiliary contact in the trip
circuit. In this case, it is not required to supervise the monitoring circuit with the breaker position – the
BLOCK
setting is
selected to “Off.” In this case, the settings are as follows (EnerVista example shown).
Figure 5-155: Trip circuit example 2
5.7.8 Digital counters
SETTINGS
CONTROL ELEMENTS
DIGITAL COUNTERS
COUNTER 1(8)
NOTE
The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring
and solid-state contact with voltage monitoring.
COUNTER 1
COUNTER 1
FUNCTION: Disabled
Range: Disabled, Enabled
COUNTER 1 NAME:
Counter 1
Range: 12 alphanumeric characters
COUNTER 1 UNITS:
Range: six alphanumeric characters
COUNTER 1 PRESET:
0
Range: –2,147,483,648 to +2,147,483,647
Trip coil
52a
UR-series device
with form-A contacts
I = current monitor
V = voltage monitor
DC–
827074A3.CDR
H1a
H1b
H1c
I
V
DC+
Bypass
resistor
R
Power supply
Resistance
Power
24 V DC
1000 O
2 W
30 V DC
5000 O
2 W
48 V DC
10000 O
2 W
110 V DC
25000 O
5 W
125 V DC
25000 O
5 W
250 V DC
50000 O
5 W
Values for resistor “R”