5-300
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
AR INITIATE MODE:
Protection AND CB
Range: Protection AND CB, Protection Only
AR BLOCK BKR1:
Off
Range: FlexLogic operand
AR CLOSE TIME BKR 1:
0.10 s
Range: 0.00 to 655.35 s in steps of 0.01
AR BKR MAN CLOSE:
Off
Range: FlexLogic operand
AR BLK TIME UPON MAN
CLS: 10.00 s
Range: 0.00 to 655.35 s in steps of 0.01
AR 1P INIT:
Off
Range: FlexLogic operand
AR 3P INIT:
Off
Range: FlexLogic operand
AR 3P TD INIT:
Off
Range: FlexLogic operand
AR MULTI-P FAULT:
Off
Range: FlexLogic operand
BKR ONE POLE OPEN:
Off
Range: FlexLogic operand
BKR 3 POLE OPEN:
Off
Range: FlexLogic operand
AR 3-P DEAD TIME 1:
0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
AR 3-P DEAD TIME 2:
1.20 s
Range: 0.00 to 655.35 s in steps of 0.01
AR 3-P DEAD TIME 3:
2.00 s
Range: 0.00 to 655.35 s in steps of 0.01
AR 3-P DEAD TIME 4:
4.00 s
Range: 0.00 to 655.35 s in steps of 0.01
AR EXTEND DEAD T 1:
Off
Range: FlexLogic operand
AR DEAD TIME 1
EXTENSION: 0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
AR RESET:
Off
Range: FlexLogic operand
AR RESET TIME:
60.00 s
Range: 0 to 655.35 s in steps of 0.01
AR BKR CLOSED:
Off
Range: FlexLogic operand
AR BLOCK:
Off
Range: FlexLogic operand
AR PAUSE:
Off
Range: FlexLogic operand
AR INCOMPLETE SEQ
TIME: 5.00 s
Range: 0 to 655.35 s in steps of 0.01
AR BLOCK BKR2:
Off
Range: FlexLogic operand