CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-265
5
5.7.5 Trip output
SETTINGS
CONTROL ELEMENTS
TRIP OUTPUT
TRIP OUTPUT
TRIP MODE:
Disabled
Range: Disabled, 3 Pole Only, 3 Pole & 1 Pole
TRIP 3-POLE INPUT-1:
Off
Range: FlexLogic operand
TRIP 3-POLE INPUT-6:
Off
Range: FlexLogic operand
TRIP 1-POLE INPUT-1:
Off
Range: FlexLogic operand
TRIP 1-POLE INPUT-6:
Off
Range: FlexLogic operand
TRIP RECLOSE INPUT-1:
Off
Range: FlexLogic operand
TRIP RECLOSE INPUT-6:
Off
Range: FlexLogic operand
TRIP SEAL-IN DELAY:
0.000 s
Range: 0 to 65.535 s in steps of 0.001
TRIP RESET:
CBaux OR Custom
Range: Pole Curr OR Custom, CBaux OR Custom,
Custom
START TMR Z2PH Inp1:
Off
Range: FlexLogic operand
START TMR Z2PH Inp2:
Off
Range: FlexLogic operand
START TMR Z2GR Inp1:
Off
Range: FlexLogic operand
START TMR Z2GR Inp2:
Off
Range: FlexLogic operand
PHASE SELECTOR RESET
DELAY: 0.500 s
Range: 0.500 to 3.000 s in steps of 0.001 s
TRIP FORCE 3-POLE:
Off
Range: FlexLogic operand
TRIP PILOT PRIORITY:
0.000 s
Range: 0 to 65.535 s in steps of 0.001
REVERSE FAULT:
Off
Range: FlexLogic operand
TRIP DELAY ON EVOLV
FAULTS: 0.000 s
Range: 0 to 65.535 s in steps of 0.001
BKR
Φ
A OPEN:
Off
Range: FlexLogic operand
BKR
Φ
B OPEN:
Off
Range: FlexLogic operand
BKR
Φ
C OPEN:
Off
Range: FlexLogic operand