5-152
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
5.5.5 FlexLogic equation editor
SETTINGS
FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
There are 512 FlexLogic entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" element
is selected as a FlexLogic entry, the associated state flag is never set to ‘1’. Press the
+/–
key when editing FlexLogic
equations to quickly scan through the major parameter types.
5.5.6 FlexLogic timers
SETTINGS
FLEXLOGIC
FLEXLOGIC TIMERS
FLEXLOGIC TIMER 1(32)
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
TIMER 1 TYPE
— Selects the time measurement unit.
TIMER 1 PICKUP DELAY
— Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY
— Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
5.5.7 FlexElements
SETTINGS
FLEXLOGIC
FLEXELEMENTS
FLEXELEMENT 1(8)
FLEXLOGIC
EQUATION EDITOR
FLEXLOGIC ENTRY 1:
END
Range: FlexLogic operands
FLEXLOGIC ENTRY 512:
END
Range: FlexLogic operands
FLEXLOGIC
TIMER 1
TIMER 1
TYPE: millisecond
Range: millisecond, second, minute
TIMER 1 PICKUP
DELAY: 0
Range: 0 to 60000 in steps of 1
TIMER 1 DROPOUT
DELAY: 0
Range: 0 to 60000 in steps of 1
FLEXELEMENT 1
FLEXELEMENT 1
FUNCTION: Disabled
Range: Disabled, Enabled
FLEXELEMENT 1 NAME:
FxE 1
Range: up to six alphanumeric characters
FLEXELEMENT 1 +IN:
Off
Range: Off, any analog actual value parameter
FLEXELEMENT 1 -IN:
Off
Range: Off, any analog actual value parameter
FLEXELEMENT 1 INPUT
MODE: SIGNED
Range: SIGNED, ABSOLUTE
FLEXELEMENT 1 COMP
MODE: LEVEL
Range: LEVEL, DELTA
FLEXELEMENT 1
DIRECTION: OVER
Range: OVER, UNDER