![GE Digital Energy L60 Instruction Manual Download Page 487](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854487.webp)
CHAPTER 6: ACTUAL VALUES
PRODUCT INFORMATION
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
6-23
6
There is an identical menu for each of the breakers.
The
BKR 1 ARCING AMP
values are in units of kA
2
-cycles. See the
COMMANDS
CLEAR RECORDS
menu for clearing breaker
arcing current records.
The
BREAKER OPERATING TIME
is defined as the slowest operating time of breaker poles that were initiated to open.
6.5 Product information
6.5.1 Model information
ACTUAL VALUES
PRODUCT INFO
MODEL INFORMATION
The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.
The rear panel on the device contains similar information.
ETHERNET MAC ADDRESS
— UR devices with firmware 7.0x and above have three Ethernet ports that can be used on three
networks. The MAC address displays for port 1. The MAC address for port 2 is one higher. The MAC address for port 3 is one
higher than port 2. In redundant mode, the MAC addresses for ports 2 and 3 are the same as port 2.
6.5.2 Firmware revisions
ACTUAL VALUES
PRODUCT INFO
FIRMWARE REVISIONS
BKR 1 OPERATING
TIME: 0 ms
MODEL INFORMATION
ORDER CODE LINE 1:
L60-A00-AAA-A0A-A0A
Range: standard GE order code format (lines 1 to 4)
SERIAL NUMBER:
Range: standard GE serial number format
ETHERNET MAC ADDRESS
000000000000
Range: standard Ethernet MAC address format
MANUFACTURING DATE:
0
Range: YYYY/MM/DD HH:MM:SS
OPERATING TIME:
0:00:00
Range: operating time in HH:MM:SS
PMU FEATURE ACTIVE:
No
Range: Yes, No
LAST SETTING CHANGE:
1970/01/01 23:11:19
Range: YYYY/MM/DD HH:MM:SS
FIRMWARE REVISIONS
L60 Relay
REVISION: 7.3x
Range: 0.00 to 655.35
Revision number of the application firmware.
MODIFICATION FILE
NUMBER: 0
Range: 0 to 65535 (ID of the MOD FILE)
Value is 0 for each standard firmware release.
BOOT PROGRAM
REVISION: 7.01
Range: 0.00 to 655.35
Revision number of the boot program firmware.
FRONT PANEL PROGRAM
REVISION: 2.01
Range: 0.00 to 655.35
Revision number of faceplate program firmware.
COMPILE DATE:
2013/09/15 04:55:16
Range: YYYY/MM/DD HH:MM:SS
Date and time when product firmware was built.