5-158
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
5.6.3 Phase comparison elements
5.6.3.1 Menu
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE COMPARISON ELEMENTS
5.6.3.2 87PC scheme (ANSI 87PC)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE COMPARISON ELEMENTS
87PC SCHEME
BREAKER FAILURE
VOLTAGE ELEMENTS
PHASE COMPARISON
ELEMENTS
87PC SCHEME
See below
ADVANCED
FAULT DETECTORS
CHARGE CURRENT
COMPENSATION
OPEN BREAKER
ECHO
87PC SCHEME
87PC FUNCTION:
Disabled
Range: Disabled, Enabled
87PC SCHEME SELECT:
2TL-TR-SPC-2FC
Range: 2TL-TR-SPC-2FC, 2TL-BL-SPC-2FC,
2TL-TR-DPC-3FC, and so on
87PC BLOCK:
Off
Range: FlexLogic operand
87PC SIGNAL SOURCE:
One Source Current
Range: One Source Current, Two Sources Current
87PC SIGNAL:
Mixed I_2-K*I_1
Range: Mixed I_2–K*I_1, Mixed I_1+I_2/K, 3I_0
87PC MIXED SIGNAL K:
0.20
Range: 0.00 to 0.25 in steps of 0.01
87PC MIXED SIGNAL
REF ANGLE: 0°
Range: 0 to 359° in steps of 1
87PC FDL PICKUP:
0.50 pu
Range: 0.02 to 15.00 pu in steps of 0.01
87PC FDL AUX:
Off
Range: FlexLogic operand
87PC FDH PICKUP:
0.75 pu
Range: 0.05 to 15.00 pu in steps of 0.01
87PC FDH AUX:
Off
Range: FlexLogic operand