5-74
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
File transfer by IEC 61850
The L60 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an
example.
1.
In the AX-S4 61850 Explorer window, click the
Tools
menu and access the SISCO File Transfer Utility.
2.
Select the
Remote AR Name
from the drop-down list. Available files appear in the
File Specification
area on the right
side of the window.
3.
With the
Copy
option active, select a file to transfer and click the
Go
button. The file is copied and displays in the
Local
list on the left side of the window.
4.
Repeat the process to transfer any other files.
Figure 5-30: File transfer by IEC 61850
5.3.4.13 Web server HTTP protocol
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
WEB SERVER HTTP PROTOCOL
The L60 contains an embedded web server and can display pages in a web browser. The web pages are organized as a
series of menus that can be accessed starting at the L60 “Main Menu.” Web pages are read-only and are available showing
DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the L60 and a
computer to an Ethernet network, then enter the IP address of the L60 Ethernet port in a web browser.
To close the port, set the port number to 0. The change takes effect when the L60 is restarted.
WEB SERVER
HTTP PROTOCOL
HTTP TCP PORT
NUMBER: 80
Range: 0 to 65535 in steps of 1