5-46
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
System functional ldName
Range: 0 to 64 VisibileString characters
Default:
This setting is similar to setting
Master functional ldName
, but is for the System logical device, which contains the UR
logical nodes modelling power system devices: breakers, switches, CTs, VTs, and so on, including interface to these such
as AC inputs, contact I/O, transducer I/O, and HardFiber I/O.
Prot functional ldName
Range: 0 to 64 VisibileString characters
Default:
This setting is similar to setting
Master functional ldName
, but is for the Prot logical device instance, which contains the
UR logical nodes modelling protection and protection related functions.
Ctrl functional ldName
Range: 0 to 64 VisibileString characters
Default:
This setting is similar to setting
Master functional ldName
, but is for the Ctrl logical device instance, which contains the
UR logical nodes modelling control and monitoring functions.
Meter functional ldName
Range: 0 to 64 VisibileString characters
Default:
This setting is similar to setting
Master functional ldName
, but is for Meter the logical device instance, which contains
the UR logical nodes modelling metering and measurement (other than PMU), including Signal Sources.
Gen functional ldName
Range: 0 to 64 VisibileString characters
Default:
This setting is similar to setting
Master functional ldName
, but is for the Gen logical device instance, which contains the
UR logical nodes modelling FlexLogic, Virtual Outputs, non-volatile latches, FlexElements, recording (for example
oscillography), security, front panel, and clock.
Location
Range: 0 to 255 ASCII characters
Default: Location
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.location. This data attribute is
provided by the protocol to allow the user to declare where the equipment is installed.
Latitude
Range: -90.000 to 90.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.latitude. This data attribute is provided
by the protocol to allow the user to declare the geographical position of the device in WGS84 coordinates -latitude.
Negative values indicate a southern latitude. WGS refers to the world geodetic system, which is used in global
positioning systems (GPS), and 84 is the current version of the standard.
Longitude
Range: -180.000 to 180.000 degrees in steps of 0.001 degree
Default: 0.000 deg
The value entered sets the value of the data attribute <LDName>/LPHD1.PhyNam.longitude. This data attribute is
provided by the protocol to allow the user to declare the geographical position of the device in WGS84 coordinates -
longitude. Negative values indicate a western longitude.