![GE Digital Energy L60 Instruction Manual Download Page 321](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854321.webp)
CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-191
5
Figure 5-97: Directional quadrilateral ground distance characteristic
Figure 5-98: Non-directional quadrilateral ground distance characteristic
GND DIST Z1 Z0/Z1 MAG
— This setting specifies the ratio between the zero-sequence and positive-sequence impedance
required for zero-sequence compensation of the ground distance elements. This setting is available on a per-zone basis,
enabling precise settings for tapped, non-homogeneous, and series compensated lines.
GND DIST Z1 Z0/Z1 ANG
— This setting specifies the angle difference between the zero-sequence and positive-sequence
impedance required for zero-sequence compensation of the ground distance elements. The entered value is the zero-
sequence impedance angle minus the positive-sequence impedance angle. This setting is available on a per-zone basis,
enabling precise values for tapped, non-homologous, and series compensated lines.
GND DIST Z1 ZOM/Z1 MAG
— The ground distance elements can be programmed to apply compensation for the zero-
sequence mutual coupling between parallel lines. If this compensation is required, the ground current from the parallel line
(3I_0) measured in the direction of the zone being compensated must be connected to the ground input CT of the CT bank
configured under the
DISTANCE SOURCE
. This setting specifies the ratio between the magnitudes of the mutual zero-
sequence impedance between the lines and the positive-sequence impedance of the protected line. Set this setting to zero
if the compensation is not to be performed. Note that internally the mutual coupling compensation is applied only if
837769A1.CDR
X
R
RE
A
C
H
RCA
DIR RCA
DIR COMP LIMIT
DIR COMP LIMIT
COMP LIMIT
COMP LIMIT
RGT BLD RCA
LFT BLD RCA
RGT BLD
-LFT BLD
"+" NON-HOMOGEN. ANG
"-" NON-HOMOGEN. ANG
837770A1.CDR
X
R
R
EAC
H
RCA
RGT BLD RCA
LFT BLD RCA
RGT BLD
-LFT BLD
RE
V
RE
ACH
RE
V
REACH
RCA
COMP LIMIT
COMP LIMIT
"-" NON-HOMOGEN. ANG
"+" NON-HOMOGEN. ANG
COMP LIMIT
COMP LIMIT
"-" NON-HOMOGEN. ANG
"+" NON-HOMOGEN. ANG