CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-197
5
Figure 5-104: Ground directional supervision logic
5.6.6 Power swing detect (ANSI 68)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
POWER SWING DETECT
POWER SWING
DETECT
POWER SWING
FUNCTION: Disabled
Range: Disabled, Enabled
POWER SWING
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
POWER SWING
SHAPE: Mho Shape
Range: Mho Shape, Quad Shape
POWER SWING
MODE: Two Step
Range: Two Step, Three Step
POWER SWING
SUPV: 0.600 pu
Range: 0.050 to 30.000 pu in steps of 0.001
POWER SW I2 SUPV ENAB:
Off
Range: FlexLogic operand
POWER SWING
I2 SUPV: 0.2 pu
Range: 0.050 to 30.000 pu in steps of 0.001
POWER SWING FWD
REACH: 50.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING QUAD FWD
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING QUAD FWD
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING FWD
RCA: 75°
Range: 40 to 90° in steps of 1
POWER SWING REV
REACH: 50.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING QUAD REV
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING QUAD REV
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING REV
RCA: 75°
Range: 40 to 90° in steps of 1
POWER SWING OUTER
LIMIT ANGLE: 120°
Range: 40 to 140° in steps of 1
POWER SWING MIDDLE
LIMIT ANGLE: 90°
Range: 40 to 140° in steps of 1
V_0 > 5 volts
RUN
Zero-sequence
directional characteristic
837009A7.CDR
AND
OR
Co-ordinating time:
pickup = 1.0 cycle, reset = 1.0 cycle
SETTING
= V_0
= I_0
Distance Source
FLEXLOGIC OPERAND
OPEN POLE OP
TIMER
t
pickup
t
reset
FLEXLOGIC OPERAND
GND DIST Z2 DIR SUPN