![GE Digital Energy L60 Instruction Manual Download Page 265](http://html.mh-extra.com/html/ge-digital-energy/l60/l60_instruction-manual_571854265.webp)
CHAPTER 5: SETTINGS
FLEXLOGIC
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-135
5
The following table lists alphabetically the operands available for the relay.
Table 5-18: L60 FlexLogic operands
RxGOOSE Boolean
On
RxGOOSE Boolean 1 On
The RxGOOSE Boolean is presently in the ON state
Virtual Input
On
Virt Ip 1 On
The virtual input is presently in the ON state
Virtual Output
On
Virt Op 1 On
The virtual output is presently in the set state (that is,
evaluation of the equation that produces this virtual output
results in a "1")
Operand type
Operand syntax
Operand description
CONTROL
PUSHBUTTONS
CONTROL PUSHBTN 1 ON
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
CYBERSENTRY
ROLE ADMIN ACT
ROLE SUPERVISOR ACT
ROLE ENGINEER ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
ROLE EXTERNAL ACT
AUTHENTICATION FAIL
UNAUTH FW ATTEMPT
UNAUTH SETTING WRITE
RADIUS SRV UNAVAILABLE
ACCT SRV UNAVAILABLE
Administrator role is active and is set to true when that is the case
Supervisor role is active and is set to true when that is the case
Engineer role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
External role is active and is set to true when that is the case
Operand set for Failed Authentication self-test and alarm
Operand set for firmware lock self-test and alarm
Operand set for settings lock self-test and alarm
Operand set for RADIUS servers unavailable self-test
Operand set for ACCOUNTING servers unavailable self-test
DIRECT INPUT/
OUTPUT CHANNEL
MONITORING
DIR IO CH1 CRC ALARM
DIR IO CH2 CRC ALARM
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level
The rate of returned direct input/output messages on channel 1 exceeded
the user-specified level (ring configurations only)
The rate of returned direct input/output messages on channel 2 exceeded
the user-specified level (ring configurations only)
ELEMENT:
87PC phase
comparison
87PC PKP
87PC OP
87PC DPO
87PC TRANS BLOCK OP
87PC FDL OP
87PC FDH OP
87PC BKR ECHO PKP
87PC V2 FDL OP
87PC V2 FDH OP
87PC dI2/dt FDL OP
87PC dI2/dt FDH OP
87PC dI1/dt FDL OP
87PC dI1/dt FDH OP
87PC I_2 FDL OP
87PC I_2 FDH OP
87PC I_1 FDL OP
87PC I_1 FDH OP
87PC RX1
87PC RX2
Phase comparison has picked up
Phase comparison has operated
Phase comparison has dropped out
Phase comparison transient blocking has operated
Overcurrent fault detector low has operated
Overcurrent fault detector high has operated
Open breaker echo of phase comparison has picked up
Advanced fault detector low, I2*Z - V2 has operated
Advanced fault detector high, I2*Z - V2 has operated
Advanced fault detector low, rate of change of the negative-sequence
current has operated
Advanced fault detector high, rate of change of the negative -sequence
current has operated
Advanced fault detector low, rate of change of the positive-sequence current
has operated
Advanced fault detector high, rate of change of the positive-sequence
current has operated
Advanced fault detector low, negative-sequence current has operated
Advanced fault detector high, negative-sequence current has operated
Advanced fault detector low, positive-sequence current has operated
Advanced fault detector high, positive-sequence current has operated
Received pulse on channel 1
Received pulse on channel 2
Operand type
State
Example of format
Characteristics
[Input Is ‘1’ (= ON) if...]