CHAPTER 5: SETTINGS
SYSTEM SETUP
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-123
5
5.4.5 Disconnect switches
SETTINGS
SYSTEM SETUP
SWITCHES
SWITCH 1(16)
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to
create interlocking functionality. For greater security in determination of the switch pole position, both the 89/a and 89/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the L60.
SWITCH 1 FUNCTION
— This setting enables and disables operation of the disconnect switch element.
SWITCH 1 NAME
— Assign a user-defined name (up to six characters) to the disconnect switch. This name is used in flash
messages related to disconnect switch 1.
SWITCH 1 MODE
— This setting selects “3-Pole” mode, where disconnect switch poles have a single common auxiliary
switch, or “1-Pole” mode where each disconnect switch pole has its own auxiliary switch.
SWITCH 1 OPEN
— This setting selects an operand that creates a programmable signal to operate a contact output to open
disconnect switch 1.
SWITCH 1 BLK OPEN
— This setting selects an operand that prevents opening of the disconnect switch. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
SWITCH 1
SWITCH 1
FUNCTION: Disabled
Range: Disabled, Enabled
SWITCH 1 NAME:
SW 1
Range: up to six alphanumeric characters
SWITCH 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
SWITCH 1 OPEN:
Off
Range: FlexLogic operand
SWITCH 1 BLK OPEN:
Off
Range: FlexLogic operand
SWITCH 1 CLOSE:
Off
Range: FlexLogic operand
SWITCH 1 BLK CLOSE:
Off
Range: FlexLogic operand
SWTCH 1
Φ
A/3P CLSD:
Off
Range: FlexLogic operand
SWTCH 1
Φ
A/3P OPND:
Off
Range: FlexLogic operand
SWITCH 1
Φ
B CLOSED:
Off
Range: FlexLogic operand
SWITCH 1
Φ
B OPENED:
Off
Range: FlexLogic operand
SWITCH 1
Φ
C CLOSED:
Off
Range: FlexLogic operand
SWITCH 1
Φ
C OPENED:
Off
Range: FlexLogic operand
SWITCH 1 Toperate:
0.070 s
Range: 0.000 to 65.535 s in steps of 0.001
SWITCH 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
SWITCH 1 EVENTS:
Disabled
Range: Disabled, Enabled