4-2-7 TROUBLE LEVEL OF SYSTEM
<< System Condition when Outdoor Unit Error is occurred >>
Not indicated on Indoor Unit and
Peripheral unit.
Indicated on Service Tool.
Indicated on Indoor Unit (*1)
and Peripheral unit.
Indicated on Service Tool.
Abnormal LED indication
Outdoor unit does not stop
Operation continues
- 14.1 Outdoor unit network
communication 1 error
- 13.1 Communication error between outdoor unit
- 14.2 Outdoor unit network communication 2 error
- 14.5 The number of indoor unit shortage (*2)
- 61.5 Outdoor unit reverse phase, missing phase wire error
- 69.1 Outdoor unit transmission PCB parallel communication error
- 9A.1 Coil1 (Expansion valve1) error
- 9A.2 Coil2 (Expansion valve2) error
- 9A.3 Coil3 (Expansion valve3) error
- A5.1 Low pressure abnormal (*3)
System Condition
Outdoor unit Condition
System is not
stopped compulsorily
Trouble Level
1
2
(*1) This will not be displayed on indoor unit which Error Report Target (function setting 47 of indoor unit) is set "for administrator".
(*2) The System condition can change to (Trouble Level 1) by changing DIP SW (SET 4-1:OFF)
(*3) Even if power is reset, this Error cannot release. In Error release, you need to solving the problem and operate the push switch and a and apply
"Error reset" (F3-40) after power restart.
(*4) When one of outdoor unit on the multi connection detects these Error, the backup operation can activate by using of remaining outdoorunit(s)
Please check each trouble shooting, and read the caution before using the backup operation.
- 62.3 Outdoorunit EEPROM acccess error
- 62.8 EEPROM data corrupted error
- 73.5 Heat Ex.1 liquid temp. sensor error
- 73.7 Heat Ex.2 liquid temp. sensor error
- 75.1 Suction gas temp sensor error
- 82.2 Sub-cool Heat Ex. gas outlet temp. sensor error
- 83.1 Liquid pipe temp. sensor 1 error
- 83.2 Liquid pipe temp. sensor 2 error
- 62.6 Inverter communication error
- 63.1 Inverter error
- 68.2 Rush current limiting resister temp. rise protection (*3)
- 71.1 Discharge Temp sensor 1 error
- 72.1 Compressor Temp sensor 1 error
- 73.4 Heat Ex. 1 gas temp sensor error
- 73.6 Heat Ex. 2 gas temp sensor error
- 74.1 Outdoor Temp sensor error
- 77.1 Heat sink Temp sensor error
- 84.1 Current sensor 1 error (*3)
- 86.1 Discharge pressure sensor error
- 86.3 Suction pressure sensor error
- 86.4 High pressure switch 1 error
- 93.1 Inverter compressor start up error (*3)
- 94.1 Trip detection (*3)
- 95.5 Comp. motor loss of synchronization (*3)
- 97.1 Outdoor unit fan motor lock error (*3)
- 97.5 Fan motor temperature abnormal (*3)
- 97.9 Fan motor driver abnormal (*3)
- A1.1 Discharge temperature 1 abnormal (*3)
- A3.1 Compressor1 temperature abnormal (*3)
- A4.1 High pressure abnormal
- A4.2 High pressure protection1
- A6.3 Outdoor Heat Ex. 1 gas temp. abnormal (*3)
- A6.4 Outdoor Heat Ex. 2 gas temp. abnormal (*3)
- AC.4 Heat sink temperature abnormal
- 67.2 Inverter PCB short
interruptation detection
Abnormal LED indication
Outdoor unit stop
System is
compulsorily stopped
(*4)
<< Error code which manual error release will be required >>
A5.1 Low pressure abnormal
84.1 Current sensor 1 error
93.1 Inverter compressor start up error
94.1 Trip detection
A1.1 Discharge temperature 1 abnormal
A3.1 Compressor 1 temperature abnormal
97.1 Outdoor unit fan motor lock error
97.5 Fan motor temperature abnormal
97.9 Fan motor driver abnormal
68.2 Rush current limiting resister temp rise protection
95.5 Compressor motor loss of synchronization
A6.3 Outdoor heat exchanger 1 gas temperature abnormal
A6.4 Outdoor heat exchanger 2 gas temperature abnormal
System is
compulsorily stopped
Abnormal LED indication
Outdoor unit stop
04-08
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......