Trouble shooting 80
Outdoor air unit- No Power
Forecast of Cause :
1. Power Supply failure
2. Outside cause
3. Electrical Component defective
Is not the breaker down?
Check Point 1 : Power supply
Instant drop -----Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line
(Neon bulb or electric equipment that may cause harmonic wave).
Check the complete insulation of grounding.
OK
Check protector open / short
If the protector is open circuit, replace it.
Check Point 2 : Check Protector (20A)
04-89
OK (No short circuit)
Check AC line (L-N) open / short
Check Point 3 : Check AC line
NG (Short circuit)
Disconnect the wire between Filter PCB and reactor,
check short circuit of AC line.
If there is short circuit, replace the Filter PCB.
Check Point 4 : Check short circuit Filter PCB
OK (No short circuit)
Connect the disconnected wire(s) on the check point 4,
disconnect the wire between Diode bridge and Capacitor,
check short circuit of AC line.
If there is short circuit, replace the Diode bridge.
Check Point 5 : Check short circuit Diode bridge
OK (No short circuit)
Connect the disconnected wire(s) on the check point 5,
disconnect the wire between Capacitor and Filter PCB,
check short circuit of AC line.
If there is short circuit, replace the Capacitor.
Check Point 6 : Check short circuit Capacitor
OK (No short circuit)
Connect the disconnected wire(s) on the check point 6,
disconnect the wire of Fan motor, check short circuit of
AC line.
If there is short circuit, replace the Power supply PCB.
Check Point 7 :
Check short circuit Power supply PCB
OK (No short circuit)
Check open / short of FAN motor
Refer to the Service Parts Information 20.
If there is short circuit, replace FAN motor.
Check Point 8 : Check Fan Motor
Disconnect the connector (CN200) on the Power supply PCB
and check the short circuit
1. DC12V line ( CN200 Pin 1- 5 )
2. DC 5V Line ( CN200 Pin 1 - 3 )
3. DC 15V-1 Line ( CN500 Pin 3 - 4 )
4. DC 15V-2 Line ( CN530 Pin 3 - 4 )
If one of them is short circuit, replace the Power supply PCB
Check Point 9 : Short circuit check on DC circuit
Disconnect the CN10 (EEV1) on the Main PCB, and check short circuit
on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, replace the EEV coil.
Check Point 10 : Check short circuit of actuators (for DC12V)
Disconnect the CNC01 (WRC) on the Main PCB, and check short circuit
on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, check the WRC wire, WRC.
Disconnect the CNB01 (Ext.Out) on the Main PCB, and check short circuit
on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, check the Ext. device or wiring.
Disconnect the CN2 (TransmissionPCB) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, replace the Transmission PCB.
Disconnect the CN22 (Interconnecting wire) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, replace the Filter PCB.
If the short circuit appears after disconnecing actuators,
replace the Main PCB.
Disconnect the CN14 (SW PCB) on the Main PCB, and check short circuit
on Main PCB CN 4 Pin 1 - 3.
If the short circuit disappears, replace the SW PCB.
Check Point 11 : Check short circuit of actuators (for DC5V)
Disconnect the CN18 (Receiver unit *Option) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 3.
If the short circuit disappears, check the wire, Receiver unit.
Disconnect the CN2 (Transmission PCB) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 3.
If the short circuit disappears, replace the Transmission PCB.
Disconnect the CN21 (Interconnecting wire) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 3.
If the short circuit disappears, replace the Power supply PCB.
If the short circuit appears after disconnecing actuators,
replace the Main PCB.
OK (No short circuit)
OK (No short circuit)
OK (No short circuit)
Summary of Contents for AB* A12GATH
Page 5: ...1 TEST RUN ...
Page 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 52: ...3 INDOOR UNIT OPERATION ...
Page 75: ...4 TROUBLE SHOOTING ...
Page 203: ...5 APPENDING DATA UNIT ...
Page 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Page 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Page 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Page 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Page 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Page 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Page 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Page 220: ...05 17 MODEL ARXH096GTAH ...
Page 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Page 225: ...6 DISASSEMBLY PROCESS ...
Page 226: ......